Introduction to grounding points of transformer core

(1) An iron yoke clamp grounding lead shall be set separately. Because if the iron core touches the upper clamp, resulting in multi-point grounding fault, the grounding current only flows inside the iron core clamp, and there is no current in the iron core grounding outgoing line, which will lead to the staff mistakenly believing that the iron core has not failed; After setting, no matter where the iron core touches the clamp, it will form a loop through two external grounding leads, so that the grounding current can be correctly detected externally.


(2) The iron core grounding strip is placed in the middle of the cross section of the yoke. In this way, no matter where the insulating bolt of the iron yoke strap is and where the fault grounding point is, the best induced voltage of the circuit is only 1 / 4 of the turn voltage, and the ZD grounding current is only about a few amps, which is much smaller than when the iron core grounding strip is placed in other positions.


(3) If it is really necessary to place the iron core grounding strip at other positions due to inconvenient on-site installation, the insulating bolt and grounding strip of the iron yoke strap shall also be placed diagonally, so as to prevent large current.

current transformer electronic split core toroidal power

prev
Today we are going to share amorphous magnetic rings
Introduction of nanocrystalline alloy 1k107 strip
next
Recommended for you
no data
Get in touch with us
Tel: +86 757 8622 8688
Mobile( WhatsApp): +86 139 2868 9494
Email: sales@transmart.net

Address
Room 1113, Block 7, TianAn Center,
31 East Jihua Road, Foshan 528200, China
Better Touch Better Business
Contact Sales at TRANSMART.
+86 757 8622 8688
Copyright © 2026 TRANSMART INDUSTRIAL LIMITED | Sitemap  | Privacy Policy
Customer service
detect