The secondary winding should be grounded when the current transformer and voltage transformer are in use

The secondary winding of the current transformer and voltage transformer should be grounded during use to prevent the high voltage from entering the low voltage through the transformer after the insulation of the transformer is broken down, which will injure the instrument and the user. Ground the secondary point of the transformer. , Which does not affect the normal use of the equipment, but also guarantees the safety of personnel and equipment.


In order to ensure safety, the secondary side of the current transformer must be grounded to protect the body and equipment when there is a high voltage danger on the secondary side of the current transformer.

Current Transformer

Current transformer function


During the production process, the use of the primary equipment in the system is monitored to ensure the safe use of the power system. The current transformer usually converts the large current of the primary circuit into a secondary small current proportional to it, and finally outputs the small secondary current to the secondary instrument, relay protection, and automatic device for use. Therefore, the current transformer is the AC current source of the electrical control, regulation, measurement and protection components, and it is also the hub of the electrical secondary circuit and the primary circuit.


Why can't the secondary side of the current transformer be open? Because the secondary circuit of the current transformer is open, the secondary current disappears, and the demagnetization effect also disappears, which will cause the magnetic density in the iron core to be very high. And because the number of turns of the secondary winding is much greater than the number of turns of the primary winding, once the secondary side is open, a very high voltage will appear, sometimes as high as several thousand volts, which not only endangers the secondary side equipment, but also serious personal life. Safety.

prev
How to make annealed nanocrystalline iron cores easy to cut
Application of Electromagnetic Core in Fault Indicator Collection Unit
next
Recommended for you
no data
Get in touch with us
Tel: +86 757 8622 8688
Mobile( WhatsApp): +86 139 2868 9494
Email: sales@transmart.net

Address
Room 1113, Block 7, TianAn Center,
31 East Jihua Road, Foshan 528200, China
Better Touch Better Business
Contact Sales at TRANSMART.
+86 757 8622 8688
Copyright © 2026 TRANSMART INDUSTRIAL LIMITED | Sitemap  | Privacy Policy
Customer service
detect